Power Modules function as power supply or battery charger; 12, 24 or 48 volts; positive, negative floating ground. Wire in parallel to create systems from 500-6,000 watts. Optional quick connect wiring kit allows swap-out of modules without system shutdown. 115/230 VAC, 50-60 Hz input. 19″ or 23″ rackmount standard. Bulkhead/shelf mounting bracket optional.
Specifications
Model | Input Amps @ Full Load 115/230V |
Output | Watts | Weight | |||
---|---|---|---|---|---|---|---|
VDC V Out |
VDC V2 |
Amps Cont.+ |
|||||
Lbs. | Kg. | ||||||
PM-12-40A | 8.5/4.3 | 13.6 | 14.3 | 40 | 560 | 12.2 | 5.5 |
PM-12-80 | 16/8 | 13.6 | – | 80 | 1000 | 15.2 | 6.9 |
PM-24-20 | 8.5/4.3 | 27.2 | 27.9 | 20 | 560 | 12.2 | 5.5 |
PM-24-40 | 16/8 | 27.2 | – | 40 | 1000 | 15.2 | 6.9 |
PM-48-10 | 8.5/4.3 | 54.4 | 55.1 | 10 | 560 | 12.2 | 5.5 |
PM-48-20 | 16/8 | 54.4 | – | 20 | 1000 | 14.0 | 6.4 |
PM-48-50 | */22 | 54.4 | – | 50 | 2500 | 34 | 15 |
VDC (V out) Measured at output terminal with oring diode VDC (V2) Measured at direct output terminal + For parallel configuration/load sharing derate output 10% * 230 VAC input only |
Performance Specifications
Input:
85 – 135/170-270 VAC (selectable), 47 – 63 Hz., 560 watt models
90 – 265 VAC, 1000 watt models
207 – 253 VAC, 2200 watt model
Power Factor:
0.7, 560W & 2200W models
0.98, 1000W models
Regulation: +/- 1% at direct output (V2); +/- 2% through “oring” diode (V out)
Ripple: 1% (Typical)
Efficiency: 80-85% @ full load
Front panel Output Voltage Adjustment Pot Range: +/- 10%
Altitude Range: Full output to 5,000 feet. Derate output current 4% per 1,000 feet to 10,000 feet max.
Temperature Rating
560 watt models: -40˚ C; Derate linearly from 100% load @ 50˚ C to 75% @ 60˚ C
1000 watt models: -20˚ C; Derate linearly from 100% load @ 50˚ C to 50% @ 70˚ C
2200 watt model: 0 – 50˚ C
Mechanical/General
- Powder coated aluminum front panel and cover
- Vinyl laminated base and cover
- 19″ Rackmount brackets provided
- Wallmount via optional brackets
- AC Input wiring:
- 560 watt units: IEC AC entry, 6′ IEC cord with NEMA 5-15 plug provided
- 1000 watt units: IEC entry, 6′ IEC power cord with NEMA 20 plug provided
- 2200 watt unit: Hardwire junction box, no power cord provided
- 1/4″ -20 Output stud (560 watt models)
- Output bus bar (1,000 and 2200 watt models) with 1/4″ – 20 bolts
- Output “OK” L.E.D.
- Multi color LED: Green = Ok, Red = Fail (1000W models only)
- Loss-of-output alarm contacts- Form C, plus loss of AC alarm contacts – Form C (1000 and 2200 watt units only)
- Front panel voltage test points
Options
- Three stage charger function with gel/ lead-acid selector Model: CFB (560 & 1000 watts only)
- Temperature compensation (for battery charging). All models.
- DC Quick Connect Wiring Kit:
- 560 watt models: QCK-3 (for 2-3 unit PM system) & QCK-6 (for 4-6 unit PM system)
- 1000 watt models: QCK-3A (for 2-3 unit PM system) & QCK-6A (for 4-6 unit PM system)
- 2200 watt model: CCK-4
- “Universal” mounting bracket; Model: UMB-PM (500 & 1KW models only)
- Metering, alarms, LVD and distribution breakers (PFM-400 or ULM-100 module options)
Protection
- Output fuse for reverse polarity
- Current limit
- Input circuit breaker
- Automatic high temp. output
power reduction (560W & 2200W models) - Forced air cooling with filter provided (560W models only)
Design Standards
- UL 1950 / EN 60950 (Safety)
- EN 50082 (Immunity)
- EN 55014 (Conducted)
- Case Size – All Models
Case Size – All Models
Height X Width* X Depth
Inches: 3.5 X 17 X 20.5
Centimeters: 13.5 X 43.2 X 52.1
*19″ mounting brackets provided